850W 通信模块电源
850W 通信模块电源
产品详情
/ PRODUCT DETAILS
850W 通信模块电源 型号:G1377-B
输入特性 Input Characteristics |
|||
项 目 Item |
技术要求 Requirement |
单 位 Unit |
备 注 Note |
交流输入电压范围 Ac input voltage range |
85~285 |
Vac |
90Vac-264V 输出满载 850W |
额定输入电压范围 Rated input voltage range |
90~264 |
Vac |
|
额定输入电压 Rated input voltage |
230 |
Vac |
|
交流输入电压频率 Frequency of ac input voltage |
44~66(额定值为 50/60) 44 ~ 66(rated 50/60) |
Hz |
|
功率因数 power factor |
≥0.90 |
|
额定输入,100%负载 Rated input, 100% load |
输入电流总谐波 Total harmonic of input current |
≤15% |
|
额定输入,100%负载 Rated input, 100% load |
启动冲击电流 Inrush Current |
≤30 |
A |
264Vac/冷态 Normal temperature condition /额定负载Rated load |
最大输入电流 Max Input Current |
≤10 |
A |
185Vac/额定负载 Rated load |
输出特性 Output Characteristics |
|||
项 目 Item |
技术要求 Requirement |
单 位 Unit |
备 注 Note |
输出电压范围 Output Voltage Range |
42-55 |
Vdc |
监控可调,所有配置出厂前配置 OK,出厂后只可通讯不可升级或其他操作。 The monitoring is adjustable, an d all configurations are OK bef ore delivery. After delivery, only communication can be perform ed, but no upgrade or other ope rations can be performed. |
额定输出电压 Rated output voltage |
48 |
Vdc |
没有监控默认 48V 输出,有监控则调整至 42V 输出 If there is no monitoring, the d efault output is 48V. If there is monitoring, the output is adjust ed to 42V |
|
额定输出电流 Output Current |
0-17.7 |
A |
|
|
效率Efficiency |
≥92% |
|
230Vac、50%-100%负载 |
|
温度系数 temperature coefficient |
±0.02 |
%/℃ |
|
|
输出纹波及噪声 Ripple and noise |
≤200 |
mVp-p |
带宽≤20MHz 20 MHZ bandwidth or less |
|
开机启动时间 Startup time |
≤3 |
S |
|
|
输出上升时间 Output rise time |
200 |
mS |
输出电压从 10%上升至额定电压的 90%时间,额定负载。 The output voltage rises from 10% to 90% of the rated voltage for the rated load. |
|
开、关机过冲幅度 On and off overshoot |
≤±5 |
%Vo |
额定输入电压,输出满载。 Rated input voltage;Output full load. |
|
动态响应 Dynamic |
过冲幅度 overshoot |
≤ ±5 |
%Vo |
25% ~50%、50%~ 75%负载跳变。由于负载的阶跃变化引起的直流输出电压变化后的恢复时间应不大于 200us,其超调量应不不超过输出电压整定值的±5%。25% to 50%, 50% to 75% load jump. The recovery time after the dc output voltage change caused by the step change of the load should not exceed 200us, and the overshoot should not exceed ±5% of the output voltage setting value. |
恢复时间recovery tim e |
≤ 200 |
µS |
||
稳压精度 Voltage regulation accuracy |
≤±0.6%*Vo |
|
|
|
电话衡重杂音电压 The telephone balances the noise voltage |
≤2 |
mV |
|
|
宽频杂音电压 |
≤50 |
|
3.4~150KHz |
Broadband noise voltage |
≤20 |
mV |
0.15~30000KHz |
|
离散杂音 Discrete noise |
≤5 |
mV |
3.4~150KHz |
|
≤3 |
150~200KHz |
|||
≤2 |
200~500KHz |
|||
≤1 |
500~30000KHz |
|||
保护特性protective characteristics |
||||
项 目 Item |
技术要求 Requirement |
单位 Unit |
备 注 Note |
|
输入欠压告警点 Enter the undervoltage alarm point |
90 |
Vac |
告警作用,不做其他处理 Alarm function, do not perform other operations |
|
输入欠压保护 Input undervoltage protecti on |
80±2 |
Vac |
|
|
输入欠压恢复点 Input the undervoltage recovery point |
85±2 |
Vac |
额定电压范围(90Vac-264Vac) Rated voltage range (90Vac-264Vac) |
|
输入过压保护 Input overvoltage protection |
290±2 |
Vac |
|
|
输入过压保护恢复点 Input overvoltage protection recovery point |
280±2 |
Vac |
|
|
输入频率保护 Input frequency protection |
<44 或>66 < 44 or > 66 |
Hz |
关闭输出,输入频率恢复至正常范围,输出自动恢复。 Turn off the output, input frequency to normal range, output automatic recovery. |
|
输出过压保护 Output overpressure protection |
≥58 |
Vdc |
锁死,断电重启后才能恢复。 Lock, power off and restart to restore. |